ТШ-0,66-1; ТШ-0,66А-1

Current transformers:

  • transformer ТШ-0.66-1 – 5-year inter-verification interval;
  • transformer ТШ-0.66А-1 – the inter-verification interval is 16 years.
Категорія:

Опис

Current transformers ТШ-0.66-1; ТШ-0.66A-1 are designed for transmission of measurement information signals to measuring, automation, signaling and control devices in alternating current electrical circuits with a frequency of 50 Hz or 60 Hz.

Current transformers ТШ-0.66-1; ТШ-0.66A-1 meet the requirements of the Technical Regulations of legally regulated measuring equipment, approved by the Cabinet of Ministers of Ukraine Resolution No. 94 of 13.01.2016, DSTU EN 61869-1, DSTU EN 61869-2.

Current transformers ТШ-0.66-1; ТШ-0.66A-1 (without busbar, with a hole for the busbar), installed on the busbars of consumers’ distribution devices.

Technical characteristics

Type, option

constructive execution

Nominal primary

current strength, A

Nominal secondary

current strength, A

Class

accuracy

The highest

voltage, kV

ТШ-0.66-1;

ТШ-0.66А-1*

300,400,500,600,

800, 1000, 1200

5

0.2; 0.5S;

0.5; 1

0.72

* – at the customer’s request, it is possible to manufacture transformers with an amorphous alloy core.

Nominal secondary load with power factor сосj 2  = 0.8 5 V×A.

Operating conditions:

– ambient air temperature from minus 45 °C to plus 40 °C;

– relative air humidity up to 98% at a temperature of plus 25 °C.

Weight, no more than 1.42 kg.

Mounting of current transformers is possible with the help of the base and spring, which are included in the delivery set, or with the help of a Din-rail, which is supplied on a separate order.

Interval:

– transformers ТШ-0.66-1 – 5 years;

– transformers ТШ-0.66A-1 – 16 years.

Overall, installation and connection dimensions of transformers ТШ-0.66-1; ТШ-0.66A-1