ЦК0220

The meter determines:
– the active component of the total electrical resistance R
– the reactive component of the total electrical resistance X
– phase shift angle between voltage and current.
Overall dimensions – meter 350 mm x 315 mm x 140 mm;
The weight of the meter is no more than 6 kg.

Опис

The ЦК 0220 phase-zero circuit parameters meter is designed for measuring the short-circuit current strength (hereinafter referred to as the short-circuit current strength), total electrical resistance, phase-zero circuit voltage in 220 V alternating current networks, with a frequency of 50 Nz, with a dead-grounded neutral.

The meter determines the active and reactive components of total electrical resistance, the phase shift angle between voltage and current as information parameters.

The meter is used to control the parameters of the phase-zero circuit at energy facilities.

The meter is manufactured in accordance with the requirements of the Technical Regulations of Low-Voltage Electrical Equipment (hereinafter referred to as the Technical Regulations), approved by the Resolution of the Cabinet of Ministers of Ukraine dated 16.12.2015 No. 1067, DSTU EN 61557-3:2014 Electrical safety of low-voltage distribution networks with a voltage of up to 1,000 V alternating current and 1500 V DC. Equipment for testing, measuring or monitoring safety devices. Part 3. Total resistance of the circuit, Technical regulations on electromagnetic compatibility of equipment, approved by the resolution of the Cabinet of Ministers of Ukraine dated 16.12.2015 No. 1077, DSTU EN 61326-1:2016 Electrical equipment for measurement, control and laboratory use. Requirements for electromagnetic compatibility. Part 1. General requirements and DSTU EN 61010-1.

Technical characteristics

The range of measurement of the current strength k.z. – from 10 A to 10,000 A.

The range of network voltage measurement is from 180 V to 245 V.

Total electrical resistance measurement range is from 0.022 W to 22 W.

Power supply from an alternating current network with a voltage of (220    ) V, a frequency of (50 ± 0.5) Нz.

Power consumption (when the MEASUREMENT button is not pressed) is no more than 15 V∙A.

The time to establish the working mode is no more than 20 s.

Duration of continuous work – 8 h. The break time before restarting is at least 25 min.

The mode of operation when measuring on objects is repeated and short-term. The interval between measurements (by pressing the MEASUREMENT button) is set by the work program (» 20 s), after which a sound signal is given, allowing the next measurement to be performed.

The working position of the meter is the horizontal location of the measuring device.

The degree of protection of the meter body is IP20 according to DSTU EN 60529:2014 Degrees of protection provided by casings (IR Code).

The meter provides measurement of phase-zero circuit parameters with one press of the MEASUREMENT button.

The meter remembers the last 10 measurement results.

The limits of the permissible relative basic error when measuring the voltage of the phase-zero circuit are ± 1%.

Working conditions of application:

– ambient air temperature from minus 10 ºС to plus 40 ºС;

– relative air humidity up to 90% at a temperature of 25 ºС.

Overall dimensions:

– measuring 350 mm x 315 mm x 140 mm;

– bags with a set of connecting wires 220 mm x 120 mm x 190 mm.

The weight of the meter is no more than 6 kg.

The average earnings per refusal is at least 6,500 h.

The average recovery time is 18 h.

The average term of service is 10 years.